Real-World Scenarios

Case studies from the field. Read the situation, decide what you would do, then reveal each step to compare your plan against a guided answer.

Sprinkler & supervisory · Advanced

Dry System Low Air Pressure on a Freezing Night

Read the full write-up

Site

Unheated loading dock protected by a dry-pipe sprinkler system with an air compressor and a low-air supervisory switch. Outside temperature is 18 °F (−8 °C). After-hours call at 11 PM.

FACP · Panel display

SUPERVISORY: LOW AIR

DRY SYSTEM 3 · UNHEATED DOCK · 27 PSI

What you find on arrival

The panel shows SUPERVISORY — LOW AIR PRESSURE on Dry System 3. The gauge on the dry-pipe valve reads 27 psi; normal is 40 psi and the valve trips near 20 psi. The compressor is running, but pressure is falling about 1 psi every 10 minutes.

What do you do?

If the pressure keeps dropping, the dry valve will trip and flood the pipe in freezing weather. What do you do?