Sprinkler & supervisory · Intermediate

Duct Detector Alarms but the Air Handler Keeps Running

Read the full write-up

Site

Medical office building, addressable FACP. AHU-2 (12,000 CFM) has a return-air duct smoke detector programmed as a supervisory that must shut the unit down. Annual test, occupied building.

FACP · Panel display

SUPERVISORY: DUCT DETECTOR

AHU-2 RETURN · ADDR 044 · FAN STILL RUNNING

What you find on arrival

You introduce test smoke at the AHU-2 duct detector. The panel posts SUPERVISORY — DUCT DETECTOR AHU-2 as expected, but the air handler keeps running. The building engineer says it 'always shut down before.'

What do you do?

The detector works, the signal is right, but the emergency control function did not happen. What do you do?