Real-World Scenarios
Case studies from the field. Read the situation, decide what you would do, then reveal each step to compare your plan against a guided answer.
Sprinkler & supervisory · Intermediate
Duct Detector Alarms but the Air Handler Keeps Running
Read the full write-upSite
Medical office building, addressable FACP. AHU-2 (12,000 CFM) has a return-air duct smoke detector programmed as a supervisory that must shut the unit down. Annual test, occupied building.
FACP · Panel display
SUPERVISORY: DUCT DETECTOR
AHU-2 RETURN · ADDR 044 · FAN STILL RUNNING
What you find on arrival
You introduce test smoke at the AHU-2 duct detector. The panel posts SUPERVISORY — DUCT DETECTOR AHU-2 as expected, but the air handler keeps running. The building engineer says it 'always shut down before.'
What do you do?
The detector works, the signal is right, but the emergency control function did not happen. What do you do?