Fire Alarm Function Testing Workstation

Simulate activating the devices in your design and watch the notification appliances respond in real time — flashing strobes, evacuation tones, and live status updates. A safe way to understand cause-and-effect before you're on the jobsite.

Simulation for training only. Real fire alarm testing must follow the manufacturer's instructions, NFPA 72, and your AHJ — and must never be performed on a live system without proper notification and authorization.

Real-World Scenarios

Case studies from the field. Read the situation, decide what you would do, then reveal each step to compare your plan against a guided answer.

Sprinkler & supervisory · Advanced

Fire Pump Running — No Alarm on the Panel

Read the full write-up

Site

High-rise office building with an electric fire pump. The monitoring company received a FIRE PUMP RUNNING supervisory at 03:14 with no accompanying waterflow or alarm.

FACP · Panel display

SUPERVISORY: FIRE PUMP

PUMP RUNNING · NO WATERFLOW · 03:14

What you find on arrival

You arrive at 04:00. The pump is running, the FACP shows only the fire-pump-running supervisory — no waterflow, no alarm, no sprinkler activation. The pump room is warm and the controller reads 'RUN — AUTO START — PRESSURE DROP.'

What do you do?

The fire pump started itself on a pressure drop with no fire. What do you do?