Real-World Scenarios
Case studies from the field. Read the situation, decide what you would do, then reveal each step to compare your plan against a guided answer.
Site
Distribution warehouse, addressable FACP with a Class B SLC of 64 devices. A severe thunderstorm passed through two nights ago.
FACP · Panel display
TROUBLE: NO RESPONSE
SLC 1 ADDR 012 · SMOKE · LOADING DOCK
What you find on arrival
The monitoring company logged 14 'NO RESPONSE — ADDR 012' troubles overnight, each clearing within minutes. Address 12 is a smoke detector at the loading dock. The panel is NORMAL when you arrive, and the facility manager wants to know why this 'random' fault keeps happening.
What do you do?
The fault isn't present right now. How do you hunt an intermittent addressable communication fault?